Abstract

In the present paper, it is first established that even though the standard Active Power Loss Sensitivity Factor (APLSF) based technique for Renewable Energy based Distributed Generation (REDG) system excels with respect to many available technical assessment indicators, its performance falls short in case of line loss reduction and power transfer capacity improvement indicators. On further investigation through Dynamic Fault Tree Analysis technique, it is found that the unsatisfactory performance of APLSF stem from neglecting reactive power loss and line reactance. Therefore, a novel apparent power loss augmented technique coined as Dynamic Loss Evaluation Indicator (DLEI) method is proposed here. The suitability of the proposed method is validated on IEEE 33 and 85 bus distribution systems for both voltage and voltage and frequency dependent load models and it is shown that the aforementioned indicators are improved along with the other indicators like voltage profile and voltage stability to name a few. For further validation, contingency and power quality analysis are also carried out and improved performance is observed in DLEI method when compared against the APLSF based method.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.