Abstract

In view of the sensitivity and selectivity problems in DFIG (doubly-fed induction generator) wind farm collector line protection, a new adaptive distance protection scheme is proposed. First, according to the geometric distribution characteristics of the collector line voltage and current, the equation of voltage drop from the relaying point to the fault point is established and the adaptive setting coefficient is calculated. On this basis, a new adaptive distance protection criterion is formed according to the phase relationship between the fault current and the measured current. Wind farm simulation tests on RTDS verify that, the proposed method is well adaptable to different operation modes, strongly immune to the fault resistance and unaffected by the weak feed characteristics of the wind generator collector system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.