Abstract
In the case of terminal fault of long line, the failure protection of traditional circuit breaker has the problem of refusing to operate due to the insufficient sensitivity of voltage locking elements. A new circuit breaker failure protection scheme based on station area information sharing is proposed in this paper. The new scheme will replace the protection export signal with the actual protection criterion. In addition, it sets up two current transformers to detect whether the breaker is cut off after the circuit breaker is cut off, and checks the redundant current of the bus, which can improve the accuracy of the current detection. Besides, it uses reclosing checkout voltage device signal to supplement the original compound blocking signal. Theoretical analysis and simulation results show that the scheme can effectively cover the full length of the transmission line and has high reliability.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Materials Science and Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.