Abstract
The magnitude optimum (MO) technique provides a non-oscillatory closed-loop response for a large class of process models. However, this technique is based on a transfer function model that requires precise process identification and extensive computations. In the present paper, it is shown that a close relation exists between multiple integrations of the process step response and the MO criterion. Due to this relation, the MO criterion can be more simply achieved. Some practical guidelines for performing multiple integrations and for re-tuning controller parameters are also given.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.