Abstract

In this paper, a new method for identification of dominant source of harmonic generation in PCC bus is presented. In the proposed method, using superposition along with the concept of critical impedance method, new indices are defined and a novel algorithm is presented. In this algorithm, unlike the critical impedance method, there is no need to exact value of customer side harmonic impedances. Also, it is unlikely that the proposed algorithm leads to incorrect identification of the dominant source, even when the contribution of both sides is close to each other. The analysis is verified by running simulations on the modified IEEE 13-bus industrial distribution system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.