Abstract

Any sudden change in the configuration or the loading of an electrical network causes power swings between the load concentrations of that network. In order to prevent the distance protection from tripping during such conditions, a power swing blocking device is often utilized. Conventional power swing blocking devices cannot cope with very fast power swings of up to 5 Hz/sec. This paper presents a new power swing blocking principle that has the ability to immediately clear the block when a fault occurs within the relay trip zone. This is demonstrated for extremely fast swings (greater than 5 Hz/sec) and even for two phase operation (during single pole tripping). This new principle is in a form which can be implemented on an existing digital distance protection relay. Results are presented based on extensive simulation studies carried out on a typical 400 kV system, using the Electromagnetic Transient Program (EMTP) software.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.