Abstract

In this part of the article, a literary review of the methods of stationary calculations of air coolers operating in dehumidifying or frost conditions is carried out. The approaches used at the moment are reviewed, namely: dehumidification coefficient method; logarithmic enthalpy difference method (LMED); equivalent dry-bulb temperature method (EDT); as well as -NTU method (efficiency number of heat transfer units) for calculating counterflow chilled water coils. Their main differences are shown and the key expressions used in them are given. A comparison of the advantages and disadvantages of the considered methods showed the rationality of using -NTU approach due to the possibility of its application for both design and verification calculations of heat exchangers. Since the classical -NTU method is not directly applicable to dehumidifying or frost conditions, it becomes necessary to adapt it to the calculations of air coolers of all types (both counterflow and parallel-flow air coolers without phase transition of the cooling fluid, and for cases with its phase transition) to correctly describe the effect of the above processes on heat exchange.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call