Abstract
This paper introduces a smart operation strategy based on model predictive control (MPC) to optimize the performance of hydronic radiant floor systems in office buildings and presents results from its implementation in an actual building. Our MPC approach uses dynamic estimates and predictions of zone loads and temperatures, outdoor weather conditions, and HVAC system models to minimize energy consumption and cost while meeting equipment and thermal comfort constraints. It includes data-driven building models estimated and validated using data from an actual building, and deploys an optimizer based on constraint linear/quadratic programming with hard comfort bounds that yields a global minimum with predicted exogenous disturbances. The MPC results show 34% cost savings compared to baseline feedback control during the cooling season and 16% energy use reduction during the heating season. Also, the radiant floor system with the predictive controller shows 29–50% energy savings when compared with a baseline air delivery system serving two identical thermal zones located in the same building.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.