Abstract

This paper describes a new method for determining the introduction limit of DGS (distributed generation system) when DGS is introduced into distribution system of which the voltage is generally controlled by LCT (load-tap changing transformer) and LDC (line drop compensator). Nowadays, small scale DGS is being introduced into power distribution systems. But in that case, it is difficult to properly maintain the terminal voltage of low voltage customers within a permissible range. This paper reveals some correlations between the traditional voltage regulation method by LCT and LDC and the output of DGS, and also presents a method for determining the permissible introduction limit of DGS under proper voltage regulation of the power distribution system. This proposed method is applied to a 22.9 kV class power distribution system, and its validity is proofed through the simulation results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.