Abstract

In a chiller plant, primary or critical sensors are used to control the system operation while secondary sensors are installed to monitor the performance/health of individual equipment. Current sensor fault detection and diagnosis (SFDD) approaches are not applicable to secondary sensors which usually are not involved in the system control. Consequently, a hybrid multiple sensor fault detection, diagnosis and reconstruction (HMSFDDR) algorithm for chiller plants was developed. Machine learning and pattern recognition were used to predict the primary sensor faults through the comparison of the weekly performance curves. With the primary sensor signals reconstructed, the secondary sensor faults were estimated based on mass and energy balance. By applying the algorithm with various logged plant data and comparison with site checking results, a maximum of 75% effectiveness could be achieved. The merits of the present approach were further justified through off-site sensor testing which reinforced the usefulness of proposed HMSFDDR algorithm.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.