Abstract

Second-order generalized integrator (SOGI) based phase-locked loops (PLLs) are widely used for grid synchronization in single-phase grid-connected power converters. Previously, the estimated frequency of the PLL stage is fed back to the front-end SOGI block to make SOGI-PLLs frequency-adaptive, which increases the implementation complexity, and makes the tuning sensitive, thus reducing stability margins. Alternatively, a frequency-fixed SOGI-based PLL (briefly called FFSOGI-PLL) is proposed to ensure stability and simple implementation in this letter. It is commonly known that the in-phase and quadrature-phase signals generated by the frequency-fixed SOGI are of different amplitudes in the presence of frequency drifts, which causes second-harmonic ripples in the estimated parameters of the PLL loop. To deal with this issue, a simple yet effective method is developed in FFSOGI-PLL. The standard SOGI-PLL is first introduced, followed by the working principle and small-signal model of FFSOGI-PLL. The FFSOGI-PLL is then compared with the SOGI-PLL in terms of stability and transient performance. Finally, experimental results are presented to demonstrate the effectiveness of FFSOGI-PLL.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.