Abstract

This paper presents experimental measurements of boiling heat transfer in a 1.067 mm inner diameter tube, using liquid crystal thermography for wall temperature measurement. The study was motivated by the two-phase microchannel pumped cooling loop, a recent technology proposed for thermal management of tomorrow's high-end electronics. The working fluid was FC-72, which is a dielectric coolant and measurements were obtained in a closed loop test facility. A unique flow boiling onset was observed whereby a large wall temperature gradient travels along the tube. During flow boiling conditions, wall temperature fluctuations have been observed. The use of a thermographic technique has added insight into the flow boiling characteristics and acts as a partial flow visualization method. Local heat transfer coefficients are presented and compared with correlations for both macro- and microchannels. The heat transfer coefficient is found to be influenced by the heat flux at a lower mass flux but only mildly at a higher mass flux.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.