Abstract
Electromagnetic time reversal (EMTR) is drawing increasing interest in short-circuit fault location. In this letter, we investigate the classic EMTR fault location methods and find that it is not necessary to reverse the obtained signal in time which is a standard operation in these methods before injecting it into the network. The effectiveness of EMTR fault location method results from the specific similarity of the transfer functions in the forward and reverse processes. Therefore, we can inject an arbitrary type and length of source in the reverse process to locate the fault. Based on this observation, we propose a new EMTR fault location method using direct convolution. This method is different from the traditional methods, and it only needs to pre-calculate the assumed fault transients for a given network, which can be stored in embedded hardware. The faults can be located efficiently via direct convolution of the signal collected from a fault and the pre-stored calculated transients, even using a fraction of the fault signal.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Electromagnetic Compatibility
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.