Abstract
Thyristor controlled series capacitor (TCSC) is placed in transmission line to enhance its power transfer capability. However, several relaying methods experience the challenges of voltage and current inversion, nonlinear behavior of MOV and sub-synchronous oscillations in the presence of TCSC. Furthermore, power swing causes unwanted trip and severely affects the protection schemes due to the modulation of relaying signals for a TCSC-compensated line. Even, fault detection is not possible due to power swing blocking (PSB) element which blocks distance relay when impedance trajectory lies inside the relay trip zone. To overcome the problem associated with TCSC and PSB operation within the duration of power swing, a fault identification technique, based on multiplication of Teager Kaiser Energy Operators (TKEOs) of negative sequence (NS) current and voltage phasors, is proposed. It has been tested in numerous fault cases in various system conditions and compared with the existing schemes. The proposed technique can be implemented with a threshold which is a major advantage of it. Availability of local end relay voltage and current data make the scheme reliable and fast. To validate the proposed scheme, a WSCC 9-bus system with consideration of 400 kV, 50 Hz has been simulated and tested using EMTDC/PSCAD software.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.