Abstract

Occupancy, which refers to the occupant count in this paper, is one of the main factors affecting the energy consumption of commercial buildings. It is important for both building managers and energy simulation engineers to understand how an entire building’s energy consumption varies with different occupancy levels in the process of building automation systems or in assessments of building performance with benchmarking lines. Because commercial buildings usually have large scales, complex layouts and a large number of people, it is a challenge to simulate the relationships between an entire building’s energy consumption and occupancy. This study proposes a fast method for calculating the influence of occupancy on the energy consumption of commercial buildings with different building layouts and existing occupancies. Other occupant behaviors, such as the opening of windows and adjustment of shading devices, are comprehensively reflected in two basic building parameters: the balance point temperature and the total heat transmission coefficient of the building. This new method can be easily used to analyze how building energy varies with occupancy without a physical building’s energy model. An office building in Shanghai is taken as a case study to validate the proposed method. The results show that the coefficient of determination R2 between the calculated value and actual value is 0.86, 0.8 and 0.71 for lighting, cooling and heating energy, respectively, which is suitable in engineering applications.