Abstract

The aim of this work is to include the distance-protection behavior in direct methods for transient stability assessments. In this way the direct methods assess an electric-power system’s behavior more realistically and hence more reliably. In order to consider the delayed tripping zones of distance-protection relays, the time component was added to the Lyapunov energy function. The main innovation is that the dwell time of the post-fault impedance trajectory inside various tripping zones is calculated based on the speed of the transformation between the kinetic and the potential energy parts of the Lyapunov function. It enables the identification of unwanted trips during power swings. The tripping-zone settings can be revised accordingly. The method was verified by a comparison between the direct method and the well-known, time-domain, numerical-simulation method on a single-machine, infinite-bus test system where the results have to be identical. The application of the proposed method on a multi-machine power system gives good results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.