Abstract

ABSTRACTA trip-point modulation strategy is proposed for single-phase uninterruptible power supply inverters with an LC filter, which operates simultaneously with pulse-width modulation, named dual-modulation (DM) control. Current estimation and offset current approximation are used conjointly to facilitate the proposed control law. It is shown analytically that the DM control leads to reduced total harmonic distortion (THD) and gains fast transient-state recovery. The simulation and experimental results demonstrate significant amelioration to THD and dynamic state compared to proportional–integral–derivative control under both linear and non-linear loads.