Abstract
In this paper, a control technique based on system modeling of three-phase LC-filtered uninterruptible power supply (UPS) voltage source inverters (VSIs) is presented. The presented technique has the ability to improve the dynamic response of the UPS system. The control technique is established in the dq reference frame of the UPS system. The reference currents required in the control algorithm are obtained through proportional-integral (PI) regulators. The PI regulators express the reference current components by regulating the output voltages in the d- and q-axes. Besides, a virtual time constant is included in the switching functions which offer an opportunity to adjust the current dynamics as desired. Unlike the existing control approaches, the proposed control technique does not need an extra active damping signal. The feasibility of the proposed technique is confirmed through simulation results in MATLAB/Simulink environment.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.