Abstract

In order to overcome the shortcomings of the present accuracy assessment methods of power system dynamic simulation, this paper focuses the permanent single phase short-circuit fault which occurs in a large probability in power grids,and selects the typical electrical quantities which is very concerned in engineering after the fault happened. A time-scale based error criteria on simulation validation is proposed, and a comprehensive error criteria according to the average errors between simulation data and actual data is proposed to evaluate objectively the simulation accuracy of the typical electrical quantities. Considering the variation characteristics of the electrical quantities, the simulation accuracy evaluation of a single electrical element is expended to the simulation accuracy evaluation of the entire network, so not only the comprehensive evaluation about the model and its parameters but also the information for model modification and parameter correction can be obtained. The effectiveness of the proposed method is verified by the numerical results on the New England 10 Unit 39 Bus powers system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.