Abstract
Aiming at the influence of nonlinear loads on the quality of power grid, a shunt active power filter (SAPF) topology is proposed. According to this topology, the mathematical model of the three-phase shunt active power filter is established. Based on the model, it's transfer function is deduced, and the current controller is designed on account of PI control strategy. By analyzing the limitation of the PI controller in current tracking control method used for active power filters, a composite control strategy combining repetitive control with PI control method is proposed to improve the steady performance of the control system. Experimental results demonstrate that the current control method combining repetitive control with PI control method has a high steady-state compensation accuracy, which can effectively suppress harmonic currents caused by nonlinear loads and greatly improve grid current waveform.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.