Abstract

The results of the condensation heat transfer enhancement and pressure drop of HFC-134a by using the electrohydrodynamic (EHD) technique are presented. The test section is a horizontal tube-in-tube heat exchanger where the refrigerant flows in the inner tube and water flows in the annulus. The outer tube is a smooth copper tube havign outer diameter of 21.2 mm. Two types of inner tubes, smooth and micro-fin copper tubes, are tested. The outer diameter and length of both inner tubes is 9.52 mm and 2.5 m, respectively. A stainless steel cylindrical electrode of 1.47 mm in diameter is placed in the center of the tube. Experiments are conducted under conditions providing mass flux of 400 kg/m2s, saturated temperature of 40°C, heat flux of 20 kW/m2 and applied voltage of 2.5 kV. The experimental results indicate that the EHD enhancements of the smooth tube are higher than those of the micro-fin tube over the range of average quality. The maximum heat transfer enhancements for smooth and micro-fin tubes are 1.1. times and 1.08 times, respectively. For a smooth tube, the pressure drop induced by EHD is considerably small. However, the application of EHD in a micro-fin tube can lead to 10% increase in the pressure drop.