Abstract

A study was undertaken to determine if improved accuracy can be obtained using different induction motor models for bus transfer simulations where the loads have low inertias. Bus transfer simulations are presented using five different models. Based on a comparison of these simulations, separate motor models for the disconnect period, the period immediately after reenergization, and the longer time period during which bus voltage and motor speeds are restored are recommended.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.