Abstract

In the multi-infeed HVDC system, the interaction between inverter stations is an important factor that triggers the propagation of commutation failure. This paper aims to study the interaction mechanism of inverter stations and propose a reasonable method to evaluate the commutation failure risk. Firstly, based on the modified switching function, the commutation failure component is formulated to describe the commutation process and transient characteristics of inverter station during the commutation failure. Then, the analytical calculation method is studied to reflect the commutation voltage fluctuation under the influence of AC fault and commutation failure. On this basis, the commutation failure risk is assessed by comparing each valve’s maximum commutation area with the minimum commutation area required for blocking. By analyzing the commutation failure risk under different grounding impedances, it is possible to identify the critical grounding inductance that causes a remote commutation failure. Based on the multi-infeed HVDC system in PSCAD/EMTDC, the validity and accuracy of the proposed method and commutation failure component are verified.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.