Abstract

Constant power loads (CPLs) in power systems have a destabilizing effect that gives rise to significant oscillations or to network collapse, motivating the development of new methods to analyse their effect in AC and DC power systems. A sine qua non condition for this analysis is the availability of a suitable mathematical model for the CPL. In the case of DC systems power is simply the product of voltage and current, hence a CPL corresponds to a first–third quadrant hyperbola in the loads voltage–current plane. The same approach is applicable for balanced three-phase systems that, after a rotation of the coordinates to the synchronous frame, can be treated as a DC system. Modelling CPLs for single-phase (or unbalanced poly-phase) AC systems, on the other hand, is a largely unexplored area because in AC systems (active and reactive) power involves the integration in a finite window of the product of the voltage and current signals. In this paper we propose a simple dynamic model of a CPL that is suitable for the analysis of single-phase AC systems. We give conditions on the tuning gains of the model that guarantee the CPL behaviour is effectively captured.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call