Abstract

The voltage source converter based high voltage direct current (VSC-HVDC) system is a practical solution to improve renewable energy integration, flexible consumption, and wide-range complementarity. Because the DC line fault must be cleared within a few milliseconds, a reliable and rapid identification of faulty lines and poles is crucial. Unfortunately, the traditional backup protection cannot respond to internal faults fast enough and is sensitive to fault resistance. What is worse is that a double-pole-to-ground fault with unequal positive-pole and negative-pole fault resistances cannot be identified by most of the existing protection methods. The paper proposes a pilot backup protection based on directional traveling wave and waveform similarity for VSC-HVDC transmission lines to compensate for the drawbacks. The fault characteristic of 1-mode directional traveling waves and the waveform similarity of instantaneous currents of DC lines are elaborated theoretically. Based on the analyses, the protection is established, and the four-terminal VSC-HVDC grid is modeled in PSCAD and OPAL-RT. Detailed theoretical analyses and extensive simulation/experiment results have proven that the proposed protection scheme has higher reliability, selectivity, rapidity, and sensitivity. Compared with the existing backup protections, the proposed protection scheme has superiorities in fault resistance and distance tolerance (2,000 Ω and the entire length of DC lines), fault differentiation of double-pole-to-ground fault with unequal positive-pole and negative-pole fault resistances, immunity from signal noise and measurement error interference, and quicker fault judgment (less than 4 ms).© 2017 Elsevier Inc. All rights reserved.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call