Abstract

Adopting CO2 as an alternative gas of SF6 in a gas circuit breaker from the environmental viewpoint, a 72kV-31.5kA class CO2 gas circuit breaker (CO2-GCB) model, which does not contain SF6 gas at all, was designed, and produced. In the CO2-GCB model, some effective technologies for current interruption by CO2 gas were adopted; namely, puffer pressure enhancing techniques utilizing arc energy during a current interruption and ablation phenomena of a polymer element located in the puffer cylinder. As a result of current interruption and electric insulation tests, the CO2-GCB model achieved practical levels of performance. Furthermore, it was found by carrying out a life cycle assessment (LCA) that the CO2-GCB model could reduce the global warming impact by about 40% compared to the latest SF6 gas circuit breaker in the same rating for 20 years operation including one maintenance opportunity.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.