Abstract

In this study, the cooling capacity and the pressure drop of a condenser for 10kW refrigerator unit were experimentally investigated. The performance characteristics of the condenser was studied by changing the fin shape(4 types), fin pitch(5 types), tube row(4 types) and air flow rate(6 types), using the calorimeter. The optimum heat exchanger specifications were selected by comparing the capacity and the pressure drop of the condenser. In order to select the heat exchanger suitable for the condenser for 10kW refrigerator unit, both the cooling capacity and the pressure drop should be considered. From the condenser performance test by pin type, the wavy pin was selected. The optimal performance of the condenser for 10kW refrigerator unit was observed at the fin pitch of 3 mm, the tube row of 4 row, and the air flow rate of 90㎥/min.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.