Abstract
In this study, the air-side cooling capacity and pressure drop of an evaporator for a refrigerator unit were experimentally investigated. Using the calorimeter, the performance of the evaporator was verified by changing the fin shape, fin pitch, tube row and air flow rate. The experimental apparatus consisted of the calorimeter which functioned as a constant temperature and humidity chamber and the refrigeration cycle. In order to select the heat exchanger suitable for the evaporator, both air-side cooling capacity and pressure drop should be considered at the same time. From the evaporator performance test by pin type, wavy pin was selected. The optimal performance of the evaporator was observed at the fin pitch of 5 mm, the tube row of 6 row, and the air flow rate of 40㎥/min.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korean Society of Mechanical Technology
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.