Abstract

In this study, we investigate simulation studies to confirm the removal of smoke through ventilation when the subway car is on fire and stopped in an underground subway tunnel, by using Fire Dynamics Simulator (FDS) which is being upgraded by NIST. The structure of subway tunnel and train for simulation modeling are based actual data from Seoul metropolitan subway. The main purpose of this study is to assure the removal efficiency of the ventilation when changing the ventilation capacity between 2.0 m/s and 3.0 m/s. The results of the study shows that carbon monoxide (CO) and carbon dioxide () are reduced by about 35% as the ventilation capacity is increased by 0.5 m/s. This study also performs the grid sensitivity verification of FDS for improved accuracy of the results. To find the effective size of the grid, three cases are simulated and the results are compared.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call