Abstract
In this work, nucleate pool boiling heat transfer coefficients(HTCs) of pure water are measured on horizontal 26 fpi low fin, Turbo-B and Thermoexcel-E square surfaces of 9.53 mm length. HTCs are taken from 10 <TEX>$kW/m^2$</TEX> to critical heat flux for all surfaces. Test results show that critical heat fluxes(CHFs) of all enhanced surfaces are greatly improved as compared to that of a plain surface. CHFs of water on the 26 fpi low fin surface, Thermoexcel-E surface, and Turbo-B are increased up to 320%, 275%, and 150% as compared to that of the plain surface, respectively. CHF of the Turbo-B enhanced surface is lower than that of the 26 fpi low fin surface due to the surface geometry. The heat transfer enhancement ratios of the Thermoexcel-E surface, low fin surface and Turbo-B enhanced surface are 1.6~2.9, 1.6~2.1, 1.4~1.7 respectively in the range of heat fluxes tested. Judging from these results, it can be said that these types of enhanced surfaces can be used in heat transfer applications at high heat fluxes.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have