The airpollutant may accelerate degradation of power line facilities, and may reduce the life of the electric facilities. In case of korea, there are a tendency that the density of air pollution may be increased by industrial development. while lack of research activity and establishment of a countermeasure on this issue. Recently the occurrence of electricity failure have been reduced on the power transmission and distribution lines. but the occurrence of electricity failure by insulator itself has been increased. It means that we should have develop more clear technique for detection of the wrong insulator. In this study to provide a method for detection of the insulator failure or effective management of the troubled insulator, we analyze the chemical composition of the insulator which used on power distribution line at the sea side locations. To define the relation between insulation and corona intensity, we design and develop an corona detector. We define the variation of insulation by pollution changes on the insulator and verify quantitative relation between corona and insulations using the corona detector.