Abstract
Current rating of a power cable can be calculated by the maximum allowable temperature in an insulating material considering the heat transfer from cable conductor. Therefore, it is very important to calculate the current rating using electrical equivalent circuit by calculated cable thermal circuit parameters but, it has not been fully investigated yet. In this paper, in order to determine the current rating of power cable, conventional calculation method has been reviewed considering the conductor resistance, loss factor of sheath, dielectric losses and thermal resistances based on the maximum allowable temperature of 345 kV 2500 ㎟ XLPE cable. To confirm the calculation result of the current rating, the conductor temperature should be examined whether it reaches the maximum allowable temperature by the thermal equivalent circuit of the cable. Then, utilizing EMTP (Electro-Magnetic Transient Program) which is a conventional program for electrical circuit, the thermal equivalent circuit was transformed to an electric equivalent circuit using an analogous relationship between thermal circuit and electrical circuit, and temperature condition including cable conductor, sheath, cable jacket could be calculated by the current rating of 345 kV 2500 ㎟ XLPE cable.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Transactions of The Korean Institute of Electrical Engineers
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.