Abstract
In this paper, three current controllers for a grid-connected PCS using an LCL filter are compared and analyzed. Current controllers discussed in this paper are linear controllers such as PI (proportional-integral), PR (proportional-resonant), and DB (deadbeat) controller. Both transient and steady state responses of each controller are compared through both simulation and experiment. Although the DB controller has the fastest transient response and the lowest THD in the steady state, the DB controller has two cycles delay of current response in the steady state and has the stability problem which can be occurred due to variation of the system parameters. On the one hand the responses of PR controller are not much different from that of DB controller but the other hand that are not only strong to noise of grid current but also have smaller THD than PI controller. Considering the response time and stability issue of three controllers, the PR controller has the best performance among three controllers and thus can be strongly recommended as a current controller for a grid-connected PCS.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Transactions of the Korean Institute of Power Electronics
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.