Abstract

This paper describes magnetic field on power cable in underground transmission systems. Based on specification which is being used in domestic power utility, magnetic field was analyzed in accordance with line arrangement, line burial depth and phase spacing. Magnetic field magnitude and its trend were understood in each circuit type such as double circuits, triple circuits and quadruple circuits of underground transmission systems. In addition, magnetic field was analyzed according to phase arrangement changing in each circuit. Finally, the proper phase arrangement configuration type was suggested by the evaluation of analysis result. Magnetic field was calculated by using Biot-Savart's law. According to the evaluated magnetic fields based on phase layout configuration in each circuit, it figured out that each of magnetic fields was different. As a result, this paper proposes a proper phase layout configuration for generating minimum magnetic field. It is evaluated that the phase layout configuration in each circuit proposed in this paper can be used at actual underground transmission systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.