Abstract
The purpose of this study is to evaluate the airtightness performance of New Han-ok and to supply fundamental data for standards establishment. Air leakage testings were accomplished by means of blower door test in 26 bedrooms of 16 Han-oks located in Jeonnam happy villages. Followings are results. 1) Air change per hour at 50 Pa(ACH50) is located on 8.42~78.38. 2) No correlation between ACH50 and volumes, floor area, above grade surface area. 3) The more wood structural elements are exposed, attached spaces, wooden sliding and casement windows, the less airtightness performance. 4) An Airtightness with ACH50/20(NL, Normalized leakage) is located on 0.42~3.92 and building leakage class following F(4%), G(11%, sufficiently leaky, No need mechanical ventilation), H(4%, Need of cost-effective tightening), I(31%), J(50%) by a single-story house the normalized leakage of ASHRAE.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of the Korea Institute of Ecological Architecture and Environment
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.