Abstract

There is little known on the airtightness performance of residential buildings in China. The present study intends to investigate the airtightness performance of ten detached houses in China's cold area using “blower door test”. The thermal infrared imager and smoke pencil were used to find out the typical air leakage places in the building envelope.Test results show that the air change rate at the pressure difference of 50 Pa of the tested houses varies from 1.89 h−1 to 0.84 h−1 with a mean value of 1.42 h−1. The typical air leakage places happen at the reserved holes in the outer wall that were not well filled after construction, the frames of window and door that were not fitted correctly and the draught seal was deformed, and the check valves at the inlets of the discharge flue and exhaust airway in the house.The tested detached houses were ranked by their airtightness performance. The total joint length of the opening part of the windows and doors was estimated for each detached house and a linear correlation between the n50 and the joint length of the opening part of the windows and doors was examined.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.