Abstract

Heat transfer and pressure drop of horizontal heat exchangers with different configurations and installations numerically characterized. Three different heat exchangers were used and shaped as linear, wavy, and horizontal slinky, respectively. Installation depth was set from 0.5m to 3.0m and pipe spacing was ranged from 0.3m to 2.1m. The results showed that heat transfer rate and pressure drop were increased with the increase in the installation depth and the pipe spacing. The horizontal slinky heat exchanger carried more heat compared to others due to the greater effective heat transfer surface area per installation area. In terms of a ratio of heat transfer rate to pressure drop indicating the system efficiency, the linear heat exchanger performed better than others. On the other hand, the horizontal slinky heat exchanger was the most effective with respect to a ratio of heat transfer rate to installation cost.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.