Abstract

This article reports an experimental study on the performance of horizontal double tube counter-flow heat exchanger. Due to the modicum in the heat transfer surface area, the overall heat transfer coefficient is enhanced. Cu-nanoparticles are added to the cold water in the annulus of the heat exchanger, however, the inner tube that contains the hot water is rotated. The inner tube is made of copper with 25.4mm outer diameter with a thickness of 2mm, while the outer tube, which is made of transparent Acrylic Plexiglass, has an outer diameter of 76.2mm and 5mm thickness. Cu–water nanofluid is prepared at volume fractions of 1–3% and the inner tube is rotated with speed from 0 to 500rpm. Results demonstrated a remarkable enhancement in the rate of heat transfer due to the nanoparticles addition as well as the inner tube rotation. Consequently, the effectiveness and the transfer number units (NTU) of the heat exchanger are augmented. Optimization between heat transfer augmentation and the pressure drop penalty is carried out. Finally, the use of the nanofluid has a little penalty in pressure drop in compared with the inner tube rotation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.