Abstract

In this study, the temperature, the absolute humidity, and the turbulent flow characteristics of exhaust air and supply air in the mixer were studied while changing the shape of the mixer of the white smoke reducing heat exchange system. Using Solidworks, the mixer of the white smoke reduction heat exchange system was created by 3-D model. Also, the mixed flow of supply air and exhaust air inside the mixer under the uniform inlet conditions was computed, using the solidworks flow simulation. Two types of improvement models were selected by using a perforated plate and a guide vane as a turbulent mixing flow control method of the mixer. The mean temperature and mean absolute humidity of the mixture were greatly decreased according to the internal shapes of Case 1, 2, and 3. The temperature difference between the inlet and outlet of the mixer Case 3 was 26℃. The exit temperature and absolute humidity reduction rates of Case 3 were 26.2% and 48.1%, respectively, compared with Case 1.