Abstract

In this study, the characteristics of the heat flow on SA(supply air) side of the white smoke reducing heat exchange system according to the change of SA velocity were analyzed in the winter condition (outside temperature 0℃). Also, the mixing process of SA and the EA(exhaust air) is presented in the psychrometric chart to confirm the possibility of reducing white smoke. Solidworks flow simulation was used to analyze the heat flow on the heat exchange system under uniform conditions. As the inflow velocity of SA increased, the temperature of SA decreased due to the convective heat transfer improvement due to the active flow in SA system. And the outlet temperature and absolute humidity of the mixing zone decreased significantly. At SA velocity 7 m/s, the outlet temperature and absolute humidity decreased to about 58% and 82%, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.