In active distribution networks (DNs), distributed energy resources (DERs) must be disconnected from the grid prior to automatic reclosing actions. Many scholars have proposed non-voltage checking reclosing methods, but a significant challenge arises; many substations lack line-side voltage transformers (LSVTs), making these schemes impractical. To address this, we introduce a time-limited adaptive automatic reclosing (TLAR) method that integrates DERs’ anti-islanding protection (AIP) with automatic reclosing. This method estimates the AIP action time using bus-side voltage measurements before the system-side protection (SSP) is tripped and adjusts the reclosing time accordingly to enhance power supply reliability. Simulations using PSCAD validate the method’s effectiveness. The TLAR method is well-suited for distribution lines without conditions for non-voltage checking, is cost-effective, easy to implement, and contributes to power system stability.