Islanding detection is the essential basis for the safety and protection of dc microgrids. Due to the advantages of rapid detection speed and small nondetection zone, the positive feedback islanding detection technique has attracted much interest in recent years. The implementation of a positive feedback loop facilitates the islanding detection for dc microgrids, but it may reduce the system stability margin at the grid-connected state. In this article, the dc output impedance model of voltage source converter and distributed generators are developed to reveal the dynamic interactions and instability mechanism accurately between the two subsystems considering the impact of islanding detection with voltage positive feedback of selected frequency (VPFOSF). Then, the stability region of the interconnected system based on the output admittance model is derived to guide the design method of the damping compensator. Moreover, a grid-current-based active-damping control scheme is further proposed to mitigate instability caused by the VPFOSF loop. Thus, the conflict among islanding detection rapidity, power quality, and grid-connected system stability is effectively addressed. In the end, both the simulations and experimental results are provided to validate the effectiveness of the proposed control method.