To investigate the shear performance of assembled bamboo scrimber (BS)-lightweight concrete (LC) connection systems, three groups of nine BS-LC shear connections were fabricated in this work using BS, LC, dowels, and grout. The experimental parameters included the dowel diameter and fabrication process (cast-in-place vs. assembly). Push-out tests were conducted on the specimens, and traditional linear variable displacement transducer (LVDT) measurements and the advanced digital image correlation (DIC) technique were employed to determine performance indicators such as the cross-section slip of composite members. Subsequently, the method for calculating the shear capacity of assembled BS-LC connection systems was theoretically analyzed. The research results showed that the load-slip curves measured by DIC were highly correlated with those measured by LVDT, thus, validating the reliability of the DIC data. According to the DIC data, the variations in slip of the shear connection over the interface height were further analyzed. An equation for calculating the shear capacity of dowel shear connectors was proposed based on theoretical analysis with comprehensive consideration of the experimental indicators such as the failure mode, load-slip curve, shear stiffness, and shear capacity of the specimens. The theoretical calculation values were in good agreement with the experimental results.