Abstract

A transient model of airflow and heat transfer in an indoor ice rink and a quasi-steady model of its refrigeration system have been coupled and used to simulate their response to the time dependent ambient conditions and operating schedule for a typical meteorological year. The results for two different cases show that it is possible to reduce significantly the time of operation of the compressors and the energy consumption of the refrigeration system by simultaneously reducing the ceiling emissivity and increasing the secondary coolant temperature without affecting the quality of the ice.