Abstract

Cables with cross-bonded cable sheaths are predominantly used in high-voltage ac systems. Existing frequency-domain models of such cables use ABCD-parameters, which may cause numerical problems in the high-frequency region, or Y-parameters. The existing Y-parameters model excludes bonding wire impedances which may result in inaccurate estimates of the magnitude or frequency of the cable input impedance at resonant frequencies. This letter extends the formulation of an existing Y-parameters model to include bonding wire impedances. The proposed extended formulation is validated against a cable model in commercially available EMT-type software, in frequency- and time domain. For a certain bonding wire impedance model, the proposed Y-parameters model is shown to have a lower magnitude of the cable input impedance at resonant frequencies compared with a model excluding bonding wire and grounding impedances.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.