Abstract

Ion-current density is a significant indicator of electromagnetic environment under high voltage direct current lines. To improve measurement accuracy and convenience, this paper concluded factors that affect measurement results and a wireless measurement method was proposed. Wilson plate kind of sensor was designed according to the IEEE standard. The ion current was measured and digitalized by the measurement device, and the signal was transmitted to the computer via wireless sensor networks. The data were analyzed and recorded by automatic measurement software. Finally, the measurement system was calibrated and some field tests had been performed, the results show that the measurement system possesses the merits of good accuracy, simple structure, convenient operation, and high stability and reliability. The maximum current measurement error is less than 3%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.