Abstract

A new prediction method with an interior light sensor for the workplane illuminance in daylighting control systems is introduced. Based on radiosity theory, the spatial distributions of daylight and electric light in the space are discussed and the prediction method is developed. An experimental verification of the technique is performed in an outdoor test-room for a double-glazed window system with a motorized venetian blind integrated between the two glazings. Electric light and daylight predictions were performed in accordance with the proposed method. The results showed that the electric light workplane illuminance can be predicted with high accuracy (±5 lux error with a linear correlation) and that the daylight workplane illuminance can be predicted within ±20 lux (with a linear correlation) for any sky conditions (overcast, clear sky, or variable) with the window system controlled to prevent direct daylight transmission. This method is useful for integrated control of motorized daylighting devices and dimmable electric lights.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.