This paper focuses on the control of the negative sequence component of the wind turbine (WT) short circuit current. In many applications the negative sequence component is suppressed partially or entirely. Full negative sequence current suppression control would reduce the line-to-line short circuit current to the level of the load current or even to zero, thus interfering with the proper functioning of the conventional protection devices. To overcome this problem, the extension of the existing grid code has been proposed, which would require WT to inject a clearly defined level of negative sequence current. The injected current will additionally reduce the negative sequence voltage and improve the voltage phase symmetry. However, negative sequence current injection will limit the control capability of the WT in the positive sequence. The effect of different control options has been demonstrated using simulation on a test network and conclusions deduced.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.