Abstract

A wind-tunnel study has been carried out to assess wind loads on parapets of two buildings. Local pressure coefficients were measured on models with a length to height ratio ( L/ H) of 1:1 and 2:1. Most of the results were obtained for full-scale equivalent parapet heights of 1 and 2 m and for wind directions of 0°, 15°, 30°, 45°, 60°, 75° and 90°. The local wind load on the parapet was found to be approximately 30% larger at the windward corner of the building than at the mid-span location. Maximum parapet loads for the low building model were approximately 30% larger than those for the cubical model; however, the parapet height does not influence the critical design parapet loads.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.