Abstract

This paper presents a comparison between the wind-induced foundation loads measured on a type L6 transmission line tower during a field study in the UK and those computed using the UK Code of Practice for lattice tower and transmission line design (BS8100). In this work, the Code provisions have been generalised to give the wind-induced strain in each of the tower legs immediately above the foundation as a function of wind direction and wind speed at the top of the tower. The complete data set from the field monitoring has been decomposed to provide a similar formulation for comparison purposes. The analysis shows excellent agreement between the Code calculations and the measured results, within the overall accuracy of the field data. This indicates that, at least for the tower type examined here, the existing design Code provides a reliable transformation of the local wind speed at the top of the tower into tension and compression loads on the foundations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.